Εκτός αποθέματος
For fixed installation in lighting networks, power and signal systems,
wiring in distribution boards, machines and devices.
Technical characteristics:
– Manufactured according to DIN VDE 0281, part 3
– Rated voltage:
– H05V-U from 0.50mm² to 1.00mm²: U0/U – 300/500V
– H07V-U from 1.50mm² to 10mm²: U0/U – 450/750V
– Test voltage:
– H05V-U from 0.50mm² to 1.00mm²: 2000V
– H07V-U from 1.50mm² to 10mm²: 2500V
– Maximum conductor temperature: +70°C
– Maximum conductor temperature at short circuit for 5 sec: +160°C
– Ambient temperature: -30°C to +50°C
– Minimum temperature during unstallation: -5°C
– Minimum bending radius during installation:
– For diameters up to 10mm – 10D
– For diameters over 10mm – 15D
– D – cable height
– Flame test: flame retardant BDS IEC 332-1
Construction:
– Copper conductors
– Flexibility class 1 according to DIN VDE 0295 (HD 383)
– Insulation: PVC
Insulation colour:
– white, gray, black, blue, brown, red, yellow-green